i-ADVANTAGE DATA CENTER (HONG KONG)

MEGA i-ADVANTAGE: THE LARGEST INTERNET SERVICE CENTER BUILDING ( 350,000 sq. ft. ) IN THE WORLD DESIGNED TO HOST OVER 10,000 RACKS


LARGEST INTERNET SERVICE CENTER BUILDING

Floor to floor height:
• Typical floor: 4.1m ( 3.5m under beam )
• Floor loading: 5 kPa / 7.5kPa
• Total floor area: 350,000 sq.ft. gross
• Typical floor: 14,000 sq.ft. gross
• No. of Storey: 24 storeys of ISC's

[pic: floor plan]


UNINTERRUPTIBLE POWER SYSTEM

Utility Connection
• Dual feed 11kV power supply from separate HKE zone substations
• Dual feed telecom connection from separate telephone exchanges

Electricity Supply

• Main Supply: 2000 KVA Transformers
• UPS: 400KVA UPS modules with n+l configuration per floor, 30 min. battery back up time, dual power supply risers
• EPS: 2000KVA generator sets ( 24-hour continuous full supply )
• Earthing: Separate data center clean earth

[pic: power supply]
[pic: low voltage switch board]
[pic: battery rack]
[pic: isolation transformer]
[pic: dedicated diesel generator]


INDUSTRIAL GRADE AIR CONDITIONERS

• Indoor temperature at 20 +/- 2 Degree Celsius
• Relative humidity at 50% +/- 10 %
• Direct expansion type or Chilled Water Type CRAC unit

[pic: computer room air conditioning]


PRODUCTION SERVERS


We use only the best and most reliable brands of hardware to provide the best services to our customers. Our servers are Compaq ProLiant ML370 G3 Xeon 3.06GHz/512KB Cache, 2GB DDR RAM, 146GB UltraSCSI Hard Drive, designed for a 24/7 web serving environment.

[pic: global operation center]
[pic: servers in rack]
[pic: rack in Internet service center]
[pic: private cage]
[pic: private s.u.i.t.e]


SPARE SERVERS


For every 3 production servers we keep 1 online spare server. If a production server fails, it will be immediately replaced with a spare server, and the latest backup will be restored. In this way, ICDSoft can offer you a 99.9% uptime guarantee.


NETWORK RELIABILITY


• Dual TBE rooms and dual risers
• Dedicated 100mm dia G.I. Conduit for vertical backbone
• G.I. Conduit for interfloor cabling use
• Optical fibre to the building